Hume
The Problem
The Solution
Three layers, each doing a different job:
1. Static var generators: free up amps at the source
A 150 kVAr and a 10 kVAr static var generator to correct power factor and cut the reactive current drawn from the supply, freeing about 50 A on the existing connection.
2. 60 kW solar: cut the energy bill
A 60.3 kWp rooftop array (127 modules of 475 W) feeds a 50 kW three-phase Sungrow inverter. Modelled output is about 85,800 kWh a year, with around 86% used on site. At roughly 30 c/kWh the solar is estimated to pay back in about 2.1 years.
3. 215 kWh battery: cover the peaks
A PotisEdge OmniCube A215 commercial BESS is connected at the main switchboard. It charges when demand and tariffs are low, and soaks up excess solar. It discharges during the peak and early-peak periods, so the new drying room loads do not trip the existing breakers or the site's main supply protection.
Benefits and Outcomes
Key equipment
Solar modules: 127 × Risen RSM96-11-475BNDG (475 W) panels 60.325 kWp DC, low-tilt roof mount
Solar inverter: Sungrow SG50CX-P2, 50 kW three-phase, 4 MPPT, DC/AC ratio 1.20
Battery: PotisEdge OmniCube A215: 215.04 kWh LFP, 105 kW PCS, air cooled, IP54 outdoor cabinet, aerosol fire suppression
Power factor correction: Static var generators: 150 kVAr and 10 kVAr, 400 V
Metering and control: CT metering at the main switchboard, smart meter and export limiter, Modbus communications
Let's talk about your project
Contact us or call 1800 736 374 to talk about how we can help your business improve energy efficiency and reduce your energy cost.
Is your business suffering from unexplained electrical faults, failures or power spikes?
A power quality audit will identify issues and give us the data we need to design an appropriate solution for your business.